CVE-2022-2329
Schneider Electric IGSS Data Server (IGSSdataServer.exe) is affected by a CWE-190 integer overflow in versions prior to V15.0.0.22073, leading to a heap-based buffer overflow that could cause denial of service and potentially remote code execution when handling specially crafted messages. Affecte...
9.8CVSS9.7AI score0.02141EPSS
Save
CVE-2022-24324
CVE-2022-24324 affects Schneider Electric IGSS Data Server (IGSSdataServer.exe) prior to v15.0.0.22073. Root cause is a CWE-120 buffer copy without checking input size, leading to a stack-based buffer overflow and potential remote code execution when a specially crafted message is received. Affec...
9.8CVSS9.8AI score0.01204EPSS